PE Power exam · Section 8 · Transmission and Distribution Analysis
Fault current calculation: transformer short-circuit current, worked example
A fault-current calculation answers one question: if a short circuit happens here, how many amperes flow? The answer sets breaker interrupting ratings and relay settings. For a three-phase fault it is simply the voltage divided by the impedance back to the source.
- Transmission and Distribution Analysis: 8–12 of 80 exam questions
- Handbook section 5.1.5, Fault Current Analysis
- 1 worked example · 2 practice problems
How it works
The quickest version is a transformer fed from a very strong source, often called an infinite bus. The only impedance is the transformer's own, so the fault current is its full-load current divided by its per-unit impedance.
A real source has a limit, usually given as available short-circuit MVA. Convert that to a per-unit impedance on the transformer's base, add it in series, and the answer comes down.
Unbalanced faults use sequence networks. A single line-to-ground fault puts the positive, negative and zero-sequence impedances in series, and it can exceed the three-phase value when the zero-sequence impedance is small.
The formulas you need
- Full-load current
- Three-phase fault, infinite source
- Source impedance from short-circuit MVA
- Single line-to-ground fault, per unit
On exam day, look in the NCEES PE Power Reference Handbook, section 5.1.5, Fault Current Analysis. You do not need to memorise the formulas, but you do need to find them fast.
Worked example
The problem
A 2,000 kVA, 13.8 kV to 480 V three-phase transformer has an impedance of 5.75 %. Find the three-phase fault current at the 480 V terminals (a) assuming an infinite source, and (b) when the 13.8 kV system can deliver 250 MVA of short-circuit duty. Treat every impedance as reactance and ignore motor contribution.
- Transformer
- 2,000 kVA, 13.8 kV to 480 V
- Impedance
- 5.75 %
- Source
- (a) infinite, (b) 250 MVA
Step 1: Full-load current on the 480 V side
Step 2: (a) Infinite source
Step 3: Source impedance on the 2 MVA base
Step 4: Total impedance
Step 5: (b) With the real source
Answer
(a) About 41,800 A. (b) About 36,700 A, roughly 12 % lower. The infinite-source figure is the larger of the two, so it is the safe side when choosing an interrupting rating.
Common mistakes
- Using the primary voltage to find full-load current for a fault on the secondary.
- Dividing by 5.75 instead of 0.0575.
- Adding source MVA and transformer percent impedance without first putting them on one base.
- For a line-to-ground fault: forgetting the factor of 3, or counting a neutral impedance once instead of three times.
Practice problems
Work each one on paper first, then open the answer.
1. A 750 kVA, 480 V transformer has 5 % impedance. Assuming an infinite source, find the three-phase fault current at its secondary.
Show the answerHide the answer
About 18,040 A
A, and A.
2. At a solidly grounded bus, pu and pu, with 1.0 pu voltage before the fault. Find the three-phase and the single line-to-ground fault currents in per unit.
Show the answerHide the answer
4.0 pu and 5.0 pu
Three-phase: pu. Line to ground: pu, which is the larger one here.
PE Power course · Lesson 8.4 · 8 min
Watch this topic as a video lesson
Lesson 8.4, Fault current analysis, is part of the PE Power Exam Pass. The first section of the course is free with a VoltIQ account, so you can try the lessons before you pay anything.
- A 8-minute animated video that walks through the topic step by step
- A printable fill-in-the-blank workbook
- A field book that shows where to look in the reference handbook
- Five practice questions with worked solutions
Keep going
Not sure where you stand? The free PE Power diagnostic has 15 questions, scored by topic, with an explanation for each.
Take the diagnosticWritten by VoltIQ Academy for exam preparation. The example and practice problems are our own. VoltIQ Academy is not affiliated with or endorsed by NCEES. This page is study material, not design guidance for a real installation.