PE Power exam · Section 4 · Circuit Analysis
Per-unit system: explanation, worked example and practice problems
The per-unit system rewrites every voltage, current and impedance as a fraction of a base value. Once everything is on one base, transformers drop out of the circuit, and a network with several voltage levels becomes one series circuit you can add up.
- Circuit Analysis: 10–15 of 80 exam questions
- Handbook section 3.1.3, Per Unit System
- 1 worked example · 2 practice problems
How it works
Start with two choices. Pick one base power, , for the whole system. Pick one base voltage in one zone, usually the rated voltage of a generator or a bus. The base voltage of every other zone then follows from the transformer ratios, so you do not get to choose it.
Each zone gets its own base impedance and base current from those two numbers. A per-unit value is the actual value divided by the base of the zone it sits in.
Nameplate impedances are given on the equipment's own rating. A transformer marked 8 % means 0.08 per unit on its own MVA and kV. Before you add it to anything else, move it to the system base.
The formulas you need
- Base impedance
- Base current
- Change of base
On exam day, look in the NCEES PE Power Reference Handbook, section 3.1.3, Per Unit System. You do not need to memorise the formulas, but you do need to find them fast.
Worked example
The problem
A 25 MVA, 13.2 kV generator with a subtransient reactance of 0.15 per unit feeds a 30 MVA, 13.2/69 kV transformer with 8 % reactance. The transformer supplies a 69 kV line with a reactance of 12 Ω. A three-phase fault occurs at the far end of the line. Ignore resistance and pre-fault load. Find the fault current in the line and in the generator.
- Generator
- 25 MVA, 13.2 kV, 0.15 pu
- Transformer
- 30 MVA, 13.2/69 kV, 8 %
- Line
- 12 Ω at 69 kV
- Base chosen
- 30 MVA, 13.2 kV at the generator
Step 1: Set the bases
Use 30 MVA everywhere. The generator zone is 13.2 kV, so the transformer ratio makes the line zone 69 kV.
Step 2: Move the generator to the 30 MVA base
Its voltage base is unchanged, so only the MVA ratio applies.
Step 3: Transformer
It is already rated 30 MVA, so it stays at 0.08 pu.
Step 4: Put the line in per unit
Step 5: Add the series reactances and solve
Step 6: Convert back with each zone's base current
Answer
About 748 A in the 69 kV line and about 3,910 A in the generator. The per-unit current is the same in both zones, 2.98 pu. Only the base changes.
Common mistakes
- Adding the generator's 0.15 pu straight in. It is on a 25 MVA base and must be scaled to 0.18 pu first.
- Adding the line's 12 Ω to per-unit numbers. Ohms and per unit never mix.
- Converting the line current with the 13.2 kV base current. Use the base of the zone where you want the answer.
Practice problems
Work each one on paper first, then open the answer.
1. A transformer is rated 20 MVA with 6 % impedance. What is its impedance in per unit on a 100 MVA base at the same voltage?
Show the answerHide the answer
0.30 pu
pu.
2. A 4.16 kV zone uses a 10 MVA base. Find the base impedance and the base current.
Show the answerHide the answer
1.73 Ω and 1,388 A
and A.
PE Power course · Lesson 4.3 · 9 min
Watch this topic as a video lesson
Lesson 4.3, Per-unit system, is part of the PE Power Exam Pass. The first section of the course is free with a VoltIQ account, so you can try the lessons before you pay anything.
- A 9-minute animated video that walks through the topic step by step
- A printable fill-in-the-blank workbook
- A field book that shows where to look in the reference handbook
- Five practice questions with worked solutions
Keep going
Not sure where you stand? The free PE Power diagnostic has 15 questions, scored by topic, with an explanation for each.
Take the diagnosticWritten by VoltIQ Academy for exam preparation. The example and practice problems are our own. VoltIQ Academy is not affiliated with or endorsed by NCEES. This page is study material, not design guidance for a real installation.