PE Power exam · Section 4 · Circuit Analysis
Symmetrical components: explanation, worked example and practice problems
Symmetrical components split any unbalanced set of three phasors into three balanced sets: positive, negative and zero sequence. Each balanced set can be solved on a single-phase circuit, which is what makes unbalanced faults workable by hand.
- Circuit Analysis: 10–15 of 80 exam questions
- Handbook section 3.1.2, Symmetrical Components
- 1 worked example · 2 practice problems
How it works
Positive sequence rotates a-b-c, the way the system normally runs. Negative sequence rotates a-c-b and appears whenever the phases are unequal. In a motor it produces a field turning backwards, which is why unbalance means heat. Zero sequence is three phasors that are in phase with each other.
The operator turns a phasor by a third of a turn. Because , a perfectly balanced set has no negative or zero sequence at all.
Zero-sequence current needs a return path. In a grounded-wye system the neutral carries . With no neutral or ground return, is zero.
The formulas you need
- Zero sequence
- Positive sequence
- Negative sequence
- Back to phase a (no one-third)
On exam day, look in the NCEES PE Power Reference Handbook, section 3.1.2, Symmetrical Components. You do not need to memorise the formulas, but you do need to find them fast.
Worked example
The problem
A grounded-wye feeder carries A, A and A. Find the sequence currents referred to phase a, the neutral current, and the negative-sequence unbalance as a percentage of the positive sequence.
- Phase a
- 150 A at 0°
- Phase b
- 100 A at −120°
- Phase c
- 100 A at 120°
- System
- grounded wye
Step 1: Zero sequence: add the three phasors
Phases b and c are equal and 240° apart, so together they make 100 A pointing opposite to phase a.
Step 2: Positive sequence: turn b by 120° and c by 240°
Both land on 0°, lined up with phase a.
Step 3: Negative sequence: turn b by 240° and c by 120°
Now b sits at 120° and c at 240°, and again they sum to 100 A opposite phase a.
Step 4: Neutral current and unbalance
Step 5: Check by rebuilding phase a
Answer
= 16.7 A, = 116.7 A and = 16.7 A, all at 0°. The neutral carries 50 A and the negative-sequence unbalance is 14.3 %. The extra 50 A on phase a has been shared in thirds.
Common mistakes
- Leaving out the one-third when breaking phases into sequences, or adding one when rebuilding the phases.
- Swapping and . Positive sequence puts on phase b. Negative sequence puts on phase b.
- Adding magnitudes instead of phasors. is the positive sequence here, not the zero sequence.
Practice problems
Work each one on paper first, then open the answer.
1. During a single line-to-ground fault, A and . Find , and .
Show the answerHide the answer
300 A each, at 0°
With only phase a carrying current, each of the three sums is just , so each sequence current is A.
2. A grounded-wye load has A. What current flows in the neutral?
Show the answerHide the answer
36 A
A.
PE Power course · Lesson 4.2 · 9 min
Watch this topic as a video lesson
Lesson 4.2, Symmetrical components, is part of the PE Power Exam Pass. The first section of the course is free with a VoltIQ account, so you can try the lessons before you pay anything.
- A 9-minute animated video that walks through the topic step by step
- A printable fill-in-the-blank workbook
- A field book that shows where to look in the reference handbook
- Five practice questions with worked solutions
Keep going