PE Power exam · Section 8 · Transmission and Distribution Analysis
Voltage drop and voltage regulation: formulas and a worked example
Voltage drop is the difference between the voltage at the source end of a conductor and the voltage at the load. For most feeder problems it comes from one short formula that uses the conductor's resistance and reactance and the load's power factor.
- Transmission and Distribution Analysis: 8–12 of 80 exam questions
- Handbook section 5.1.1, Voltage Drop
- 1 worked example · 2 practice problems
How it works
Current through the conductor's resistance drops a voltage in step with the current. Current through its reactance drops a voltage 90° ahead of it. The load only notices the part of each that lines up with its own voltage, which is where the cosine and the sine come from.
The first formula below gives the drop along one conductor. A three-phase answer in line-to-line volts multiplies it by . A single-phase two-wire circuit multiplies it by 2, because the current goes out on one wire and comes back on the other.
Voltage regulation is a related number for transformers and lines. It says how far the load-end voltage rises when the load is removed, as a percentage of the full-load voltage.
The formulas you need
- One conductor
- Three-phase, line to line
- Single-phase, two wire
- Voltage regulation
On exam day, look in the NCEES PE Power Reference Handbook, section 5.1.1, Voltage Drop. You do not need to memorise the formulas, but you do need to find them fast.
Worked example
The problem
A 480 V three-phase feeder is 250 ft long and carries 200 A at 0.80 power factor lagging. Each conductor has a resistance of 0.050 Ω and a reactance of 0.040 Ω per 1,000 ft. Find the line-to-line voltage drop and express it as a percentage of 480 V.
- Feeder
- 480 V, three-phase, 250 ft
- Load
- 200 A at 0.80 pf lagging
- Conductor
- R 0.050 Ω, X 0.040 Ω per 1,000 ft
Step 1: Scale R and X to the length
Step 2: Find the sine
Step 3: Drop along one conductor
Step 4: Line-to-line drop
Step 5: As a percentage
Answer
About 5.54 V, or 1.15 % of 480 V. Leaving out the reactance would give 4.33 V, which is about 22 % too low.
Common mistakes
- Leaving out the on a three-phase feeder, or the 2 on a single-phase circuit.
- Dropping the reactance term. At 0.80 power factor it adds more than a volt in this example.
- Forgetting to scale per-1,000-ft values to the actual length.
- Dividing by the no-load voltage when the question asks for regulation. Regulation is divided by the full-load voltage.
Practice problems
Work each one on paper first, then open the answer.
1. A 240 V single-phase, two-wire circuit runs 120 ft one way and carries 30 A at unity power factor. The conductor resistance is 0.20 Ω per 1,000 ft. Find the voltage drop.
Show the answerHide the answer
1.44 V, which is 0.60 %
V. At unity power factor the reactance term is zero.
2. A transformer's secondary voltage is 495 V at no load and 480 V at full load. What is its voltage regulation?
Show the answerHide the answer
3.1 %
.
PE Power course · Lesson 8.1 · 9 min
Watch this topic as a video lesson
Lesson 8.1, Voltage drop & regulation, is part of the PE Power Exam Pass. The first section of the course is free with a VoltIQ account, so you can try the lessons before you pay anything.
- A 9-minute animated video that walks through the topic step by step
- A printable fill-in-the-blank workbook
- A field book that shows where to look in the reference handbook
- Five practice questions with worked solutions
Keep going
Not sure where you stand? The free PE Power diagnostic has 15 questions, scored by topic, with an explanation for each.
Take the diagnosticWritten by VoltIQ Academy for exam preparation. The example and practice problems are our own. VoltIQ Academy is not affiliated with or endorsed by NCEES. This page is study material, not design guidance for a real installation.