PE Power exam · Section 1 · Measurement and Instrumentation
Instrument transformers: CT and VT ratios, with a worked metering example
Instrument transformers scale primary current and voltage down to values a meter or relay can handle, usually 5 A and 120 V. Every reading taken on the secondary side has to be multiplied back up by the right ratio before it means anything.
- Measurement and Instrumentation: 6–9 of 80 exam questions
- 1 worked example · 2 practice problems
How it works
A current transformer (CT) is in series with the line. A CT marked 800:5 gives 5 A on its secondary when 800 A flows in the primary, a ratio of 160.
A voltage transformer (VT) is connected across the line. A VT marked 14,400:120 has a ratio of 120.
A wattmeter fed from both sees current scaled by one ratio and voltage scaled by the other, so the multiplier for power is the product of the two.
Everything connected to a CT secondary (leads, meter and relay) is its burden. The volt-amperes the CT must deliver is . A CT secondary must never be left open while primary current flows, because the voltage across the open terminals can rise to a dangerous level.
The formulas you need
- CT ratio
- VT ratio
- Power multiplier
- CT burden
Worked example
The problem
A 13.8 kV feeder is metered through 800:5 CTs and 14,400:120 VTs. On the secondary side the instruments read 3.2 A, 115 V line to line and 520 W of total three-phase power. Find the primary current, voltage, real power and power factor. The CT secondary circuit has a total impedance of 0.4 Ω. What burden is that at 5 A?
- CT
- 800:5
- VT
- 14,400:120
- Secondary readings
- 3.2 A, 115 V, 520 W
- CT circuit
- 0.4 Ω total
Step 1: Ratios
Step 2: Primary current
Step 3: Primary voltage
Step 4: Primary power
Power is scaled by both ratios.
Step 5: Power factor
Step 6: CT burden at 5 A
Answer
512 A, 13,800 V, 9.98 MW and a power factor of 0.816 on the primary side. The CT secondary circuit is a 10 VA burden at 5 A.
Common mistakes
- Reporting the secondary reading as if it were the primary value.
- Multiplying power by only one of the two ratios.
- Using 800 as the CT ratio. The ratio is 800 divided by 5, which is 160.
Practice problems
Work each one on paper first, then open the answer.
1. An ammeter on a 600:5 CT reads 3.5 A. What is the primary current?
Show the answerHide the answer
420 A
The ratio is , and A.
2. A CT secondary circuit totals 0.5 Ω. What burden does it place on the CT at 5 A?
Show the answerHide the answer
12.5 VA
VA.
PE Power course · Lesson 1.1 · 10 min
Watch this topic as a video lesson
Lesson 1.1, Instrument transformers & metering, is free. All you need is a VoltIQ account, and there is no card to enter.
- A 10-minute animated video that walks through the topic step by step
- A printable fill-in-the-blank workbook
- A field book that shows where to look in the reference handbook
- Five practice questions with worked solutions
Keep going
Not sure where you stand? The free PE Power diagnostic has 15 questions, scored by topic, with an explanation for each.
Take the diagnosticWritten by VoltIQ Academy for exam preparation. The example and practice problems are our own. VoltIQ Academy is not affiliated with or endorsed by NCEES. This page is study material, not design guidance for a real installation.