PE Power exam · Section 4 · Circuit Analysis
Three-phase circuits: wye, delta and power, with a worked example
A balanced three-phase circuit is three identical single-phase circuits shifted by 120°. Solve one phase, then scale up. Most wrong answers come from mixing up line and phase quantities, so the first job is always to name which one you have.
- Circuit Analysis: 10–15 of 80 exam questions
- Handbook section 3.1.1, 3-Phase Circuits
- 1 worked example · 2 practice problems
How it works
In a wye connection each load element sits between a line and the neutral point. It sees the line-to-neutral voltage, and the line current flows straight through it.
In a delta connection each element sits between two lines. It sees the full line-to-line voltage, and each line current is the phasor difference of two element currents.
Power formulas written with line quantities are the same for both connections. That is why nameplates and exam questions give line-to-line voltage and line current unless they say otherwise.
The formulas you need
- Wye
- Delta
- Real power
- Reactive and apparent power
On exam day, look in the NCEES PE Power Reference Handbook, section 3.1.1, 3-Phase Circuits. You do not need to memorise the formulas, but you do need to find them fast.
Worked example
The problem
A 4,160 V three-phase source supplies a balanced wye-connected load of per phase. Find the line current, the power factor, and the total real, reactive and apparent power. Then find the line current if the same three impedances are reconnected in delta.
- Source
- 4,160 V line to line
- Load
- balanced wye
- Per phase
- 20 + j15 Ω
Step 1: Phase voltage
A wye element sees line-to-neutral voltage.
Step 2: Impedance and power factor
Step 3: Line current
In wye, line current equals phase current.
Step 4: Power
Step 5: Reconnect in delta
Each element now sees 4,160 V. The line current and the power are three times the wye values.
Answer
In wye: 96.1 A at 0.80 power factor lagging, 553.8 kW, 415.3 kvar and 692.2 kVA. In delta the same impedances draw 288.2 A and 1,661 kW.
Common mistakes
- Putting 4,160 V across a wye element. Each one sees 2,402 V.
- Reporting the delta phase current, 166.4 A, as the line current.
- Writing with line values. With line-to-line voltage and line current the factor is .
Practice problems
Work each one on paper first, then open the answer.
1. A balanced delta load on a 480 V system draws 52 A of line current at 0.90 power factor lagging. Find the real power and the current in each delta element.
Show the answerHide the answer
38.9 kW and 30.0 A
kW. Each element carries A.
2. What is the line-to-neutral voltage of a 208 V wye system?
Show the answerHide the answer
120 V
V.
PE Power course · Lesson 4.1 · 9 min
Watch this topic as a video lesson
Lesson 4.1, Three-phase circuits, is part of the PE Power Exam Pass. The first section of the course is free with a VoltIQ account, so you can try the lessons before you pay anything.
- A 9-minute animated video that walks through the topic step by step
- A printable fill-in-the-blank workbook
- A field book that shows where to look in the reference handbook
- Five practice questions with worked solutions
Keep going
Not sure where you stand? The free PE Power diagnostic has 15 questions, scored by topic, with an explanation for each.
Take the diagnosticWritten by VoltIQ Academy for exam preparation. The example and practice problems are our own. VoltIQ Academy is not affiliated with or endorsed by NCEES. This page is study material, not design guidance for a real installation.