Power factor correction: capacitor sizing with a worked example
Power factor correction adds capacitors near an inductive load so that the capacitors, not the supply, provide the reactive power. The real power stays the same. The line current and the losses go down, and often the utility bill does too.
- Transmission and Distribution Analysis: 8–12 of 80 exam questions
- Handbook section 5.1.3, Power Factor Correction and Voltage Support
- 1 worked example · 2 practice problems
How it works
Picture the power triangle. Real power P is the base, reactive power Q is the height and apparent power S is the sloping side. A capacitor bank cancels part of the height. The base does not move.
So the size of the bank is the difference between the reactive power you have and the reactive power you want. Both come from the same P and the tangent of each power-factor angle.
Line current is proportional to S. With P fixed, the current falls in the ratio of the old power factor to the new one, and the loss falls with the square of that ratio.
The formulas you need
- Capacitor bank size
- Angle from power factor
- Line current after correction
- Line loss after correction
On exam day, look in the NCEES PE Power Reference Handbook, section 5.1.3, Power Factor Correction and Voltage Support. You do not need to memorise the formulas, but you do need to find them fast.
Worked example
The problem
A plant draws 500 kW at 0.70 power factor lagging from a 4,160 V three-phase bus. Find the capacitor bank needed to raise the power factor to 0.95 lagging, and the line current before and after.
- Load
- 500 kW at 0.70 pf lagging
- Bus
- 4,160 V, three-phase
- Target
- 0.95 pf lagging
Step 1: Turn each power factor into a tangent
Step 2: Reactive power before and after
Step 3: Bank size
In practice you would choose the next size up that is available.
Step 4: Line current before
Step 5: Line current after
Answer
About 346 kvar. The line current falls from 99.1 A to 73.0 A, a drop of 26 %, and the line losses fall by about 46 %.
Common mistakes
- Subtracting the power factors. is not a reactive power.
- Holding the kVA fixed instead of the kW. The load's real power is what does not change.
- Forgetting the square when working out the loss saving.
Practice problems
Work each one on paper first, then open the answer.
1. A 200 kW load runs at 0.80 power factor lagging. How many kvar bring it to unity power factor?
Show the answerHide the answer
150 kvar
, so kvar, and all of it must be cancelled.
2. A feeder is corrected from 0.75 to 0.90 power factor at constant kW. By what percentage do the line losses fall?
Show the answerHide the answer
30.6 %
.
PE Power course · Lesson 8.2 · 8 min
Watch this topic as a video lesson
Lesson 8.2, Power factor correction, is part of the PE Power Exam Pass. The first section of the course is free with a VoltIQ account, so you can try the lessons before you pay anything.
- A 8-minute animated video that walks through the topic step by step
- A printable fill-in-the-blank workbook
- A field book that shows where to look in the reference handbook
- Five practice questions with worked solutions