PE Power exam · Section 6 · Rotating Machines
Motor starting methods: current and torque, with a worked example
An induction motor started at full voltage draws several times its running current. Reduced-voltage starters cut that inrush, but they cut starting torque faster, so the question is always whether the motor can still break the load away.
- Rotating Machines: 5–8 of 80 exam questions
- Handbook section 4.2.3, Motor Starting
- 1 worked example · 2 practice problems
How it works
At standstill a motor behaves like a fixed impedance. Its current is proportional to the voltage applied to it. Its torque is proportional to the square of that voltage.
An autotransformer starter applies a fraction of line voltage to the motor. The motor current falls to times the locked-rotor current. The line current falls further, to , because the autotransformer steps the current down again on the supply side.
A wye-delta starter connects the windings in wye first, so each winding sees of line voltage. Line current and torque both fall to one third.
The formulas you need
- Motor current on tap k
- Line current on tap k
- Starting torque on tap k
- Wye-delta starter
On exam day, look in the NCEES PE Power Reference Handbook, section 4.2.3, Motor Starting. You do not need to memorise the formulas, but you do need to find them fast.
Worked example
The problem
A 460 V motor has a locked-rotor current of 1,450 A and a locked-rotor torque of 160 % of full-load torque. An autotransformer starter has taps at 50 %, 65 % and 80 %. The driven load needs at least 80 % of full-load torque to start. Pick the lowest tap that works and find the motor current and the line current on that tap. Would a wye-delta starter work?
- Locked-rotor current
- 1,450 A
- Locked-rotor torque
- 160 % of full load
- Taps
- 50 %, 65 %, 80 %
- Load needs
- 80 % torque to start
Step 1: Torque on each tap
Step 2: Pick the tap
Only the 80 % tap gives at least 80 % torque.
Step 3: Motor current on the 80 % tap
Step 4: Line current on the 80 % tap
Step 5: Check wye-delta
The line current would be lower, but the torque is short of 80 %.
Answer
Use the 80 % tap: 1,160 A in the motor and 928 A from the line, with 102 % starting torque. A wye-delta starter gives only 53 % torque, so it would not start this load.
Common mistakes
- Scaling torque in direct proportion to voltage. It goes with the square.
- Giving the motor current when the question asks for the line current on an autotransformer starter.
- Choosing wye-delta because its current is lowest, without checking the torque the load needs.
Practice problems
Work each one on paper first, then open the answer.
1. A motor draws 900 A locked rotor at rated voltage. During starting the bus sags to 90 % voltage. Find the starting current, and the starting torque as a percentage of its rated-voltage value.
Show the answerHide the answer
810 A and 81 %
Current: A. Torque: .
2. A motor draws 720 A of line current when started across the line in delta. What line current does it draw during the wye step of a wye-delta starter?
Show the answerHide the answer
240 A
A.
PE Power course · Lesson 6.2 · 8 min
Watch this topic as a video lesson
Lesson 6.2, Motor starting, is part of the PE Power Exam Pass. The first section of the course is free with a VoltIQ account, so you can try the lessons before you pay anything.
- A 8-minute animated video that walks through the topic step by step
- A printable fill-in-the-blank workbook
- A field book that shows where to look in the reference handbook
- Five practice questions with worked solutions
Keep going
Not sure where you stand? The free PE Power diagnostic has 15 questions, scored by topic, with an explanation for each.
Take the diagnosticWritten by VoltIQ Academy for exam preparation. The example and practice problems are our own. VoltIQ Academy is not affiliated with or endorsed by NCEES. This page is study material, not design guidance for a real installation.